AMIOZ / EXECUTIVE BRIEFING

AMIOZ, ISRAEL · SOLAR EXPANSION

More solar.
Designed around
the working farm.

A proposal to add 757.76 kWp between the central poultry sheds, balancing new solar capacity with tractor access and protection of existing roof generation.

PREPARED BY

Msc. Joseph Abinun

Blender aerial view of the two solar canopies between poultry sheds G3, G4 and G5
TWO CANOPIES / ONE WORKING FARMConcept visualization · R2
5.00METRES TOTAL HEIGHT
02New solar canopies
5.00 mMaximum total height
757.76 kWpProposed additional DC capacity
12 mProposed tractor crossing bay

THE EXECUTIVE PERSPECTIVE

01 / OPPORTUNITY

Use the space
between the sheds.

Two independent structures create additional solar area within the farm layout, without transferring their loads to the existing shed roofs.

02 / DESIGN PRIORITY

Capacity that respects
the operation.

A five-metre total height limit, transverse tractor access and shade on neighbouring panels shape the concept from the start.

03 / NEXT DECISION

Validate the concept
on surveyed ground.

Progress to survey, structural feasibility and a coordinated PV layout before fixing capacity, cost or expected annual yield.

THE PROJECT IN 30 SECONDS

See the concept. Follow the decisions.

Start above G5, cross the new structures, then move closer to see their height, tractor access and winter shadows.

A visual explanation of the engineering concept. The opening landscape is illustrative; height, access and winter-shadow views follow the R2 design geometry.

MUSIC & ENGLISH SUBTITLES · CONCEPT R2

THE SPATIAL STRATEGY

Between the sheds.
Independent of them.

Two freestanding steel canopies sit in the G3–G4 and G4–G5 gaps. Low-pitch gable roofs keep the edges beside the existing roof panels relatively low.

CONCEPT LOCATION PLANDiagram · not to scale
G1
G2
G3
G4
G5
G6
Existing shedsProposed canopiesClick a canopy to explore

CANOPY 01

Between G3 & G4

Envelope
10 × 180 m
Roof slope
5° each side
Module count
592 × 640 W
Proposed DC capacity
378.88 kWp

A separate crossing bay is reserved within this canopy. The route crosses from one side lane to the other.

G4 remains between the two canopies. The tractor crossings are separate movements through each canopy; the proposal does not create a route through a poultry shed.

Source aerial photograph of the poultry farm in Amioz
Actual site aerial reference extracted from the supplied plan.
Blender view of the canopy height beside the existing shed
5 m is the maximum overall height, including the solar modules.

AGRICULTURAL ACCESS

A crossing for a
full-size tractor.

A 12 m bay replaces the typical 6 m frame spacing at the crossing. Intermediate columns are omitted; the supporting transfer members still need structural design.

Target clear height
4.10 m
Gap between illustrative bases
10.90 m
Reference tractor height
3.606 m

Fendt 1050 Vario dimensional proxy, without an implement. Antennas, equipment, actual ground levels and structural deflection must be checked before approving access.

Explore the crossing planR2 concept plan of the 12 metre tractor crossing bay and illustrative turning path
Perspective showing a large agricultural tractor crossing under the proposed canopy with orange transfer-member envelopes
Orange members reserve space for transfer girders. Their sizes are illustrative and uncalculated.

STRUCTURE & MOUNTING

A steel frame for the farm.
Mounting designed around the modules.

Preliminary design basis for two 10 × 180 m canopies. The final panel model, steel sections and K2 attachment package remain to be selected and calculated.

RECOMMENDED DEVELOPMENT ROUTE

Independent galvanized steel frames

Use a two-column, low-pitch portal arrangement with a nominal 6 m frame grid. Reserve a 12 m crossing bay through local transfer girders, with bracing and column protection kept outside the vehicle path. Steel grade, member sizes, connections and foundations require the project engineer’s design.

K2 rail-and-clamp mounting

Develop a SolidRail or SingleRail interface to the steel purlins with K2. Confirm rail support spacing, fastener pull-out, module clamp zones and frame height. The rails do not replace the primary steel or bridge the tractor bay. K2 system reference ↗

MultiRail is a direct sheet-metal attachment option only if a compatible roof sheet is included and verified. An open purlin canopy needs a separately agreed connection. MultiRail scope ↗

THE CRITICAL GEOMETRY CHECK

About 0.46 m of gross depth at the eaves

5.00 m total ridge height4.10 m clear-height target10.00 m width · 5° gable · diagram not to scalePV eave plane ≈ 4.563 m

5.00 − 5.00 × tan(5°) = 4.563 m at the eave plane. Above a 4.10 m soffit target, only 0.463 m remains for the module, rail, purlin, beam stack and allowances.

The 12 m transfer girder may control feasibility. Demonstrate member depth, connection geometry and deflection within this envelope before confirming tractor clearance.

PROVISIONAL WEIGHT BASIS

33 kg per module. 592 modules per canopy.

Mechanical proxy: Trina Vertex N TSM-NEG19RC.20, 2382 × 1134 × 30 mm. The cited sheet covers 610–635 W, so it supports the mass and dimensions only. The project’s 640 W rating and 757.76 kWp remain planning assumptions until the exact module is selected. Trina mechanical reference ↗

Unfactored gravity quantities. These are not structural capacities or a complete load schedule.
ItemOne canopyBoth canopiesBasis
Module mass19.54 t39.07 t592 × 33 kg per canopy
Mounting budget allowance4.80 t9.59 t3 kg/m² × module area; estimating allowance, not a K2 bill of materials
Modules + mounting allowance24.33 t48.67 tExcludes structural steel, roof sheet, cables, walkways and other loads
Heavier-module sensitivity23.68 t47.36 t40 kg per panel, modules only; illustrative scenario

33 kg corresponds to about 12.22 kg/m² (0.120 kN/m²) over module area, or 0.106 kN/m² averaged over the 1800 m² canopy footprint. Average roof loads do not replace individual support reactions. Actual K2 mass must be calculated from rail lengths × kg/m plus clamps, brackets, splices and fasteners; catalogue examples range from 0.70 to 1.70 kg/m for the listed SolidRail profiles. K2 rail mass reference ↗

Why the standard K2 carport is not yet a confirmed fit

K2 publishes approximately 3.05 m clearance and a maximum 10.3 m span for the illustrated standard carport, below this project’s 4.10 m clearance target. Those published dimensions do not demonstrate the required 12 m transfer-bay configuration. A bespoke K2 proposal could be reviewed, but the catalogue product is not an approved substitute for the engineered frame. K2 carport dimensions ↗

Structural and durability checks before procurement

Combine verified dead loads with local-code wind uplift and downward pressure for an open canopy, edge and corner effects, maintenance actions, temperature movements and applicable seismic actions. Check steel stability, deflection, connections, anchor tension, foundation uplift and soil bearing. Do not treat a module test-pressure rating as the canopy’s design resistance.

Specify corrosion protection for the actual poultry-farm exposure, including ammonia and cleaning chemicals. Confirm aluminium-to-steel interfaces, approved fasteners, bonding, drainage and module suitability above a vehicle route. Place expansion joints and bracing through an engineered scheme for the 180 m length. Panels with open joints are not a waterproof roof.

EXISTING GENERATION / WINTER SHADING

The winter shadow study.

The 5 m height limit is only part of the picture. Existing roof and panel elevations strongly affect when additional shade reaches the neighbouring arrays.

Blender winter shadow view at 12:00 on 21 December
21 DECEMBER · UTC+212:00
12:0014:0016:0116:1416:30

Rendered R2 geometry; the camera also moves slightly. This geometric study does not measure annual energy output.

BASE GEOMETRY

About 16:15

First sampled afternoon intersection on 21 December, using assumed roof heights and five-minute calculation steps.

HEIGHT SENSITIVITY

About 15:30

Shade begins earlier if the receiving panels are one metre lower than assumed. A level survey is a priority.

WHAT IT MEANS

Area ≠ energy loss

The screen tests 17,280 receiving-roof points. It does not calculate annual production or module-level electrical losses.

Compare the geometry options
21 December · fixed UTC+2 · geometric screening
OptionFirst afternoon hitSample area at 16:30
10 m width / 5° · working concept16:1522.04%
8 m width / 5°16:1518.09%
14 m width / 5°16:1522.59%
10 m width / 2°16:0015.13%
10 m width / 8°16:1522.59%

A narrower roof reduces this late-afternoon sampled shade, but would need a revised module layout and likely less capacity. A flatter roof raises the eaves within the same 5 m height limit and starts shading earlier in this screen. See the report for all assumptions.

RECOMMENDATION FOR EXECUTIVE DISCUSSION

Advance to a surveyed,
engineered feasibility study.

Retain the two central canopies, the 5 m height envelope and the revised tractor bay as the working concept. Validate the critical assumptions before moving to investment or procurement.

01

Establish the survey baseline

Confirm roof and PV levels, ground profiles, routes, obstacles and the actual tractor with its implement.

02

Prove structural feasibility

Resolve the 12 m crossing bay, transfer girders, foundations and clear height under load.

03

Coordinate the PV design

Reconcile module fit, setbacks, service access, mounting and the height assumptions across models.

04

Build the investment case

Complete the electrical and grid review, validated annual yield, quantities and cost estimate.

DECISION SOUGHT

Agreement to develop and verify the concept through the next engineering stage.

Concept R2

Preliminary engineering concept. Capacity, clearance and shadow findings depend on the stated assumptions. Structural sections are illustrative; construction, procurement, production and financial approval require further verification.